ZoneCoolingSetpointMaximum
Brief Description
cooling systems located in climate zones 1b, 2b, and 3b shall be equipped with controls that have the capability to automatically restart and temporarily operate the system as required to maintain zone temperatures below a cooling setpoint adjustable up to 90°f or higher or to prevent high space humidity levels. (case study)
Index Description
Section 6.4.3.2.2 in 90.1-2004
Datapoints Description
T_cool_set: Zone Thermostat Cooling Setpoint Temperature
Assertions Description
if max(T_cool_set) >= 90F, then pass
Type Verification Description
Procedure-based
Assertions Type
Pass