LocalLoopSaturationReverseActingMin
Brief Description
Local loop performance verification - reverse acting loop actuator minimum saturation
Datapoints Description
value_sensor: Feedback sensor reading
value_setpoint: Setpoint value
command_control: Control command
command_min: Minimum control command value
Assertions Description
If the sensed data values are consistently above its set point, and after a default of 1 hour, the control command is still not saturated to minimum, then the verification fails; Otherwise, it passes.
Type Verification Description
Procedure-based
Assertions Type
Pass