ZoneTempControl

Brief Description

Zone temperature setpoint deadband >= 5f (2.77c)

Detailed Description

Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of at least 5°f within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. (case study for zone temperature reset, not for this one)

Index Description

  • Section 6.4.3.1.2 in 90.1-2016

Datapoints Description

  • T_set_cool: Zone cooling temperature setpoint

  • T_set_heat: Zone heating temperature setpoint

Assertions Description

  • T_set_cool - T_set_heat > 5F (2.77C)

Type Verification Description

Rule-based

Assertions Type

Pass