ZoneTempControl
Brief Description
Zone temperature setpoint deadband >= 5f (2.77c)
Detailed Description
Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of at least 5°f within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. (case study for zone temperature reset, not for this one)
Index Description
Section 6.4.3.1.2 in 90.1-2016
Datapoints Description
T_set_cool: Zone cooling temperature setpoint
T_set_heat: Zone heating temperature setpoint
Assertions Description
T_set_cool - T_set_heat > 5F (2.77C)
Type Verification Description
Rule-based
Assertions Type
Pass