HeatRejectionFanVariableFlowControlsCells

Brief Description

Heat rejection fan variable flow controls cells

Index Description

  • Section 6.5.5.2.2 in 90.1-2016

Datapoints Description

  • ct_op_cells: Number of operating cooling tower cells

  • ct_cells: Number of cooling tower cells

  • ct_m: Cooling tower mass flow rate

  • ct_m_des: Cooling tower design mass flow rate

  • min_flow_frac_per_cell: Minimum flow fraction per cooling tower cell

  • ct_P_fan: Cooling tower fan power

Assertions Description

  • if the number of operating cooling tower cells is equal to the maximum number of cooling tower cells then pass else fail

Type Verification Description

Procedure-based

Assertions Type

Pass