HeatRejectionFanVariableFlowControlsCells
Brief Description
Heat rejection fan variable flow controls cells
Index Description
Section 6.5.5.2.2 in 90.1-2016
Datapoints Description
number_cells_coolingtower_operation: Number of operating cooling tower cells
number_cells_coolingtower: Number of cooling tower cells
flow_mass_coolingtower: Cooling tower mass flow rate
flow_mass_coolingtower_design: Cooling tower design mass flow rate
fraction_flow_min_cell: Minimum flow fraction per cooling tower cell
power_fan_coolingtower: Cooling tower fan power
Assertions Description
if the number of operating cooling tower cells is equal to the maximum number of cooling tower cells then pass else fail
Type Verification Description
Procedure-based
Assertions Type
Pass