HotWaterPlantSizingWholePlant
Brief Description
Index Description
N/A
Datapoints Description
load_plant_water_hot: Hot water plant load
temperature_air_outdoor: Outdoor air temperature
capacity_nominal_plant_water_hot: Nominal capacity of the Hot water plant
temperature_drybulb_day_design_heating: Heating design day drybulb temperature
factor_oversizing: Oversizing factor
Type Verification Description
Procedure-based
Assertions Type
Pass
Assertions Description
if temperature_drybulb_day_design_heating is in dataset
if peak_load >= capacity_nominal_plant_water_hot / factor_oversizing
return True
else
return False
else