FanStaticPressureResetControl

Brief Description

The set point is reset lower until one zone damper is nearly wide open

Index Description

  • Section 6.5.3.2.3 in 90.1-2016

Datapoints Description

  • p_set: Static pressure setpoint

  • d_VAV_x: VAV Damper x Position (includes all VAV dampers served by the system under test

  • tol: Tolerance for VAV box damper position openings

  • p_set_min: : Minimum static pressure setpoint threshold

Assertions Description

  • if d_VAV(n) (n=1,2,…,N) < 0.9 and p_set(t) > p_set(t-1), then fail else pass

Type Verification Description

Procedure-based

Assertions Type

Pass