FanStaticPressureResetControl
Brief Description
The set point is reset lower until one zone damper is nearly wide open
Index Description
Section 6.5.3.2.3 in 90.1-2016
Datapoints Description
p_set: Static pressure setpoint
d_VAV_x: VAV Damper x Position (includes all VAV dampers served by the system under test
tol: Tolerance for VAV box damper position openings
p_set_min: : Minimum static pressure setpoint threshold
Assertions Description
if d_VAV(n) (n=1,2,…,N) < 0.9 and p_set(t) > p_set(t-1), then fail else pass
Type Verification Description
Procedure-based
Assertions Type
Pass