G36TerminalBoxVAVDamperTracking
Brief Description
Terminal box airflow control with vav damper following the guideline 36 recommendations
Index Description
Section 5.5.5.4 in ASHRAE Guideline 36-2021
Datapoints Description
command_damper_vav: VAV damper command
flow_volumetric_air_discharge: Discharge airflow rate
flow_volumetric_air_setpoint: Airflow setpoint
Type Verification Description
Procedure-based
Assertions Type
Pass
Assertions Description
if abs(flow_volumetric_air_setpoint - flow_volumetric_air_discharge) >= 0 (less than 1hr):
pass
elif abs(flow_volumetric_air_setpoint - flow_volumetric_air_discharge) < 0:
pass
if flow_volumetric_air_discharge - flow_volumetric_air_setpoint >= 0 (continously) and command_damper_vav <= 1:
pass
elif flow_volumetric_air_setpoint - flow_volumetric_air_discharge >= 0 (continuously) and command_damper_vav >= 99:
pass
else:
fail
end