G36SupplyFanStatus
Brief Description
G36 supply fan on/off requirements
Index Description
Section 5.16.1.1. in Guideline 36-2021
Datapoints Description
sys_mode: AHU system mode mode, enumeration of [‘occupied’, ‘unoccupied’, ‘cooldown’, ‘warmup’, ‘setback’, ‘setup’]
has_reheat_box_on_perimeter_zones: binary flag of If there are any VAV-reheat boxes on perimeter zones.
supply_fan_status: supply fan status (speed) [1, 0] (can be replaced by binary or numeric variables)
Assertions Description
if has_reheat_box_on_perimeter_zones == True:
if sys_mode != ‘unoccupied’ and supply_fan_status == ‘off’:
fail
else:
if sys_mode in [‘occupied’, ‘setup’, ‘cooldown’] and supply_fan_staus == ‘off’:
fail
if [‘occupied’, ‘unoccupied’] in sys_mode:
pass
else:
untested
Type Verification Description
Rule-based
Assertions Type
Pass