G36SupplyFanStatus
Brief Description
G36 supply fan on/off requirements
Index Description
Section 5.16.1.1. in Guideline 36-2021
Datapoints Description
mode_system: System operation mode
flag_reheat_perimeter: Flag indicating VAV-reheat boxes on perimeter zones
status_fan_supply: Supply fan status
Assertions Description
if flag_reheat_perimeter == True:
if mode_system != ‘unoccupied’ and status_fan_supply == ‘off’:
fail
else:
if mode_system in [‘occupied’, ‘setup’, ‘cooldown’] and status_fan_supply == ‘off’:
fail
if [‘occupied’, ‘unoccupied’] in mode_system:
pass
else:
untested
Type Verification Description
Rule-based
Assertions Type
Pass