G36SupplyFanStatus

Brief Description

G36 supply fan on/off requirements

Index Description

  • Section 5.16.1.1. in Guideline 36-2021

Datapoints Description

  • mode_system: System operation mode

  • flag_reheat_perimeter: Flag indicating VAV-reheat boxes on perimeter zones

  • status_fan_supply: Supply fan status

Assertions Description

  • if flag_reheat_perimeter == True:

  • if mode_system != ‘unoccupied’ and status_fan_supply == ‘off’:

  • fail

  • else:

  • if mode_system in [‘occupied’, ‘setup’, ‘cooldown’] and status_fan_supply == ‘off’:

  • fail

  • if [‘occupied’, ‘unoccupied’] in mode_system:

  • pass

  • else:

  • untested

Type Verification Description

Rule-based

Assertions Type

Pass