ChilledWaterHotWaterPlantSizingMultipleChillersBoilers
Brief Description
Index Description
N/A
Datapoints Description
status_equipment: Equipment status
load_plant_water: Chilled water/Hot water plant load
system_type: System type (Chiller or Boiler)
Type Verification Description
Procedure-based
Assertions Type
Pass
Assertions Description
For each timestep i:
If status_equipment[i] > 0:
duration_equipment[i] = timestep[i] - timestep[i-1]
else:
duration_equipment[i] = 0
end
equipment_load_hours = Sum(duration_equipment)
For each timestep i:
If load_plant_water[i] > 0:
duration_plant[i] = timestep[i] - timestep[i-1]
else:
duration_plant[i] = 0
end
plant_load_hours = Sum(duration_plant)
operation_ratio = equipment_load_hours / plant_load_hours
If operation_ratio >= tolerance
pass
else:
fail
end