IntegratedEconomizerControl
Brief Description
Economizer shall be integrated with mechanical cooling
Detailed Description
Economizer systems shall be integrated with the mechanical cooling system and be capable of and configured to provide partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. controls shall not false load the mechanical cooling systems by limiting or disabling the economizer or by any other means, such as hot-gas bypass, except at the lowest stage of mechanical cooling. (case study, add non-integrated economizer (check each seprate on, but not both on)
Index Description
Section 6.5.1.3 in 90.1-2016
Datapoints Description
oa_min_flow: OA minimum airflow setpoint
oa_flow: OA airflow
ccoil_out: Cooling coil transfer
Assertions Description
((oa_flow > oa_min_flow) AND (ccoil_out > 0)) never happens
Type Verification Description
Procedure-based
Assertions Type
Fail