LocalLoopSaturationDirectActingMin

Brief Description

Local loop performance verification - direct acting loop actuator minimum saturation

Datapoints Description

  • feedback_sensor: feedback sensor reading of the subject to be controlled towards a set point

  • set_point: set point value

  • cmd: control command

  • cmd_min: control command range minimum value

Assertions Description

  • If the sensed data values are consistently below its set point, and after a default of 1 hour, the control command is still not saturated to minimum, then the verification fails; Otherwise, it passes.

Type Verification Description

Procedure-based

Assertions Type

Pass