EconomizerHighLimitA
Brief Description
Fixed dry bulb economizer high limit
Detailed Description
Economizer needs to be off when high-limit condition was satisfied. y_e_hl =f($climate zone, $toa, $tra, $hoa, $hra)
Index Description
Table 6.5.1.1.3 in 90.1-2016
Datapoints Description
temperature_air_outdoor: Outdoor air temperature
temperature_air_outdoor_threshold: Outdoor air temperature threshold
flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint
flow_volumetric_air_outdoor: Outdoor air volume flow
Assertions Description
(flow_volumetric_air_outdoor > flow_volumetric_air_outdoor_setpoint_min) AND (temperature_air_outdoor > temperature_air_outdoor_threshold)
Type Verification Description
Rule-based
Assertions Type
Fail