HeatRejectionFanVariableFlowControl
Brief Description
The cooling tower fan power is 30% of the design value at 50% flow
Index Description
Section 6.5.5.2.1 in 90.1-2016
Datapoints Description
ct_P_fan: Cooling Tower Fan Power
ct_P_fan_dsgn: Cooling Tower Design Fan Power
ct_m_fan_ratio: Cooling Tower Air Flow Rate Ratio
ct_m_fan_dsgn: Cooling Tower Design Air Flow
Assertions Description
Verify that at 5% flow, the cooling tower fan power is 30% of the design value. Since simulation results might not include that exact point, we use a regression based approach to determining if the code requirement is met
Type Verification Description
Rule-based
Assertions Type
Pass