G36MinOAwoEconomizer
Brief Description
G36 minimum outdoor air control when economizer is in lockout
Index Description
Section 5.16 in Guideline 36-2021
Datapoints Description
temperature_air_outdoor: Outdoor air temperature
temperature_air_economizer_limit: Economizer lockout temperature limit
position_damper_air_outdoor: Outdoor air damper position
position_damper_air_return: Return air damper position
flow_volumetric_air_outdoor: Outdoor air volume flow
flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint
mode_system: System operation mode
Assertions Description
if economizer_lockout(temperature_air_outdoor, temperature_air_economizer_limit) and mode_system == ‘occupied’:
if flow_volumetric_air_outdoor < flow_volumetric_air_outdoor_setpoint_min (continuously (e.g. fall below the sp for a consecutive 1 hr)):
if position_damper_air_outdoor == 100 and position_damper_air_return == 0:
pass
else:
fail
elif flow_volumetric_air_outdoor > flow_volumetric_air_outdoor_setpoint_min (continuously):
if position_damper_air_outdoor == 0 and position_damper_air_return == 100:
pass
else:
fail
else:
pass (essentially untested yet)
else:
untested
Type Verification Description
Rule-based
Assertions Type
Pass