ZoneCoolingSetpointMaximum ==================================================================== Brief Description ------------------------------------------------------------------------------- cooling systems located in climate zones 1b, 2b, and 3b shall be equipped with controls that have the capability to automatically restart and temporarily operate the system as required to maintain zone temperatures below a cooling setpoint adjustable up to 90°f or higher or to prevent high space humidity levels. (case study) Index Description ------------------------------------------------------------------------------- * Section 6.4.3.2.2 in 90.1-2004 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_zone_cool_setpoint: Zone cooling temperature setpoint Assertions Description ------------------------------------------------------------------------------- * if max(temperature_air_zone_cool_setpoint) >= 90F, then pass Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass