ZoneHeatSetpointMinimum
Brief Description
Zone heating setpoint reset temperature minimum value check
Detailed Description
Heating systems located in climate zones 2-8 shall be equipped with controls that have the capability to automatically restart and temporarily operate the system as required to maintain zone temperatures above a heating setpoint adjustable down to 55°f or lower. (case study)
Index Description
Section 6.4.3.2.2 in 90.1-2004
Datapoints Description
T_heat_set: Zone Thermostat Heating Setpoint Temperature
Assertions Description
if min(T_heat_set) <= 55°F, then pass
Type Verification Description
Procedure-based
Assertions Type
Pass