ZoneHeatSetpointMinimum

Brief Description

Zone heating setpoint reset temperature minimum value check

Detailed Description

Heating systems located in climate zones 2-8 shall be equipped with controls that have the capability to automatically restart and temporarily operate the system as required to maintain zone temperatures above a heating setpoint adjustable down to 55°f or lower. (case study)

Index Description

  • Section 6.4.3.2.2 in 90.1-2004

Datapoints Description

  • T_heat_set: Zone Thermostat Heating Setpoint Temperature

Assertions Description

  • if min(T_heat_set) <= 55°F, then pass

Type Verification Description

Procedure-based

Assertions Type

Pass