VentilationFanControl
Brief Description
Ventilation fan control
Index Description
Section 6.4.3.4.4 in 90.1-2016
Datapoints Description
number_occupants: Number of occupants
heat_sensible: Zone sensible heat load
power_fan: Fan power
Assertions Description
if heat_sensible = 0 and number_occupants = 0 and power_fan != 0 then fail else pass
Type Verification Description
Procedure-based
Assertions Type
Pass