Brief Description
Cooling systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the mechanical cooling system as required to maintain zone temperatures below an adjustable cooling set point at least 5°f above the occupied cooling set point or to prevent high space humidity levels. (case study)
Index Description
Section 6.4.3.3.2 in 90.1-2016
Datapoints Description
T_cool_set: Zone Thermostat Cooling Setpoint Temperature
Assertions Description
if max(T_cool_set) - min(T_cool_set) >= 5F, then pass
Type Verification Description
Procedure-based
Assertions Type
Pass