VAVStaticPressureSensorLocation
Brief Description
Vav static pressure sensor location requirement
Index Description
Section 6.5.3.2.2 in 90.1-2016
Datapoints Description
p_fan_set: Static pressure setpoint
tol_P_fan: Tolerance for VAV box static pressure sensor
Assertions Description
if static pressure setpoint is no greater than 1.2 in of water (298.608 Pa) then pass else fail
Type Verification Description
Procedure-based
Assertions Type
Pass