DemandControlVentilation
Brief Description
Demand control ventilation verification for high-occupancy areas
Index Description
Section 6.4.3.8 in 90.1-2016
Datapoints Description
v_oa: Zone Air Terminal Outdoor Air Volume Flow Rate
s_ahu: status of HVAC system operation
s_eco: Air System Outdoor Air Economizer Status
no_of_occ: People Occupant Count
Assertions Description
If v_oa is constant over time, NO DCV presents. ii) If v_oa has two clusters, DCV with hbinary control presents. iii) v_oa is linearly correlated to o_ahu, DCV with occupant-counting based control presents
Type Verification Description
Rule-based
Assertions Type
Pass