DemandControlVentilation
Brief Description
Demand control ventilation verification for high-occupancy areas
Index Description
Section 6.4.3.8 in 90.1-2016
Datapoints Description
flow_volumetric_air_outdoor: Outdoor air volume flow
status_ahu: HVAC system operation status
status_economizer: Economizer status
number_occupants: Number of occupants
Assertions Description
If flow_volumetric_air_outdoor is constant over time, NO DCV presents. ii) If flow_volumetric_air_outdoor has two clusters, DCV with hbinary control presents. iii) flow_volumetric_air_outdoor is linearly correlated to status_ahu, DCV with occupant-counting based control presents
Type Verification Description
Rule-based
Assertions Type
Pass