ERVRatio
Brief Description
Erv ratio of at least 50%
Detailed Description
Energy recovery systems required by this section shall result in an enthalpy recovery ratio of at least 50%. a 50% enthalpy recovery ratio shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and entering exhaust air enthalpies at design conditions.
Index Description
Section 6.5.6.1 in 90.1-2016
Datapoints Description
oa_enth: OA enthalpy
ret_enth: Return air enthalpy
oa_enth_ERV: OA enthalpy after ERV
Assertions Description
(oa_enth_ERV - oa_enth)/(ret_enth - oa_enth) > = 50% happens at least once in winter design day
Type Verification Description
Procedure-based
Assertions Type
Pass