EconomizerHighLimitB

Brief Description

Differential dry bulb economizer high limit

Detailed Description

Check the 90.1-2016 table

Index Description

  • Table 6.5.1.1.3 in 90.1-2016

Datapoints Description

  • temperature_air_outdoor: Outdoor air temperature

  • temperature_air_return: Return air temperature

  • flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint

  • flow_volumetric_air_outdoor: Outdoor air volume flow

Assertions Description

  • (flow_volumetric_air_outdoor > flow_volumetric_air_outdoor_setpoint_min) AND (temperature_air_return < temperature_air_outdoor)

Type Verification Description

Rule-based

Assertions Type

Fail