InteriorLightingControlAutomaticFullOff
Brief Description
Interior lighting control automatic full off
Datapoints Description
o: Number of occupants
total_lighting_power: Reported total lighting power (not the design total lighting power)
lighted_floor_area: Area lit by the device/system considered
tol_o: Tolerance or threshold for the number of occupants below which the system is serving an unoccupied space
Assertions Description
The algorithm verifies that the device/system doesn’t serves more than 5,000 ft2 and that if it doesn’t, if occupants are not present for at least 20 minutes, the lighting power of the device/system should be less or equal to 0.02 W/ft2, otherwise, the verification fails.
Type Verification Description
Procedure-based
Assertions Type
Pass