G36FreezeProtectionStage2

Brief Description

G36 freeze protection stage 2 requirements

Index Description

  • Section 5.16.12.2. in Guideline 36-2021

Datapoints Description

  • supply_air_temp: supply air temperature

  • outdoor_damper_command: outdoor air damper

Assertions Description

  • if supply_air_temp < 3.3 (continuously 5 minutes) and outdoor_damper_command > 0 (ever in the following hour):

  • fail

  • else:

  • pass

  • if never (supply_air_temp < 3.3 (continuously 5 minutes)):

  • untested

Type Verification Description

Rule-based

Assertions Type

Pass