G36FreezeProtectionStage2
Brief Description
G36 freeze protection stage 2 requirements
Index Description
Section 5.16.12.2. in Guideline 36-2021
Datapoints Description
temperature_air_supply_setpoint: Supply air temperature
position_damper_air_outdoor: Outdoor air damper position
Assertions Description
if temperature_air_supply_setpoint < 3.3 (continuously 5 minutes) and position_damper_air_outdoor > 0 (ever in the following hour):
fail
else:
pass
if never (temperature_air_supply_setpoint < 3.3 (continuously 5 minutes)):
untested
Type Verification Description
Rule-based
Assertions Type
Pass