G36FreezeProtectionStage2
Brief Description
G36 freeze protection stage 2 requirements
Index Description
Section 5.16.12.2. in Guideline 36-2021
Datapoints Description
supply_air_temp: supply air temperature
outdoor_damper_command: outdoor air damper
Assertions Description
if supply_air_temp < 3.3 (continuously 5 minutes) and outdoor_damper_command > 0 (ever in the following hour):
fail
else:
pass
if never (supply_air_temp < 3.3 (continuously 5 minutes)):
untested
Type Verification Description
Rule-based
Assertions Type
Pass