CHWReset
Brief Description
Chilled water supply water temperature reset
Detailed Description
Chilled-water systems with a design capacity exceeding 300,000 btu/h supplying chilled water to comfort conditioning systems shall include controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature. where ddc is used to control valves, the set point shall be reset based on valve positions until one valve is nearly wide open or setpoint limits of the system equipment or application have been reached. (case study)
Index Description
Section 6.5.4.4 in 90.1-2016
Datapoints Description
temperature_air_outdoor: Outdoor air temperature
temperature_air_outdoor_max: Outdoor air temperature upper threshold
temperature_air_outdoor_min: Outdoor air temperature lower threshold
temperature_water_chilled: Chilled water temperature
flow_mass_water_chilled: Chilled water mass flow rate
temperature_water_chilled_setpoint_max: Chilled water maximum temperature setpoint
temperature_water_chilled_setpoint_min: Chilled water minimum temperature setpoint
Assertions Description
When flow_mass_water_chilled > 0, temperature_water_chilled <= temperature_water_chilled_setpoint_max and temperature_water_chilled >= temperature_water_chilled_setpoint_min; When flow_mass_water_chilled <= 0 , always pass
Type Verification Description
Rule-based
Assertions Type
Pass