CHWReset

Brief Description

Chilled water supply water temperature reset

Detailed Description

Chilled-water systems with a design capacity exceeding 300,000 btu/h supplying chilled water to comfort conditioning systems shall include controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature. where ddc is used to control valves, the set point shall be reset based on valve positions until one valve is nearly wide open or setpoint limits of the system equipment or application have been reached. (case study)

Index Description

  • Section 6.5.4.4 in 90.1-2016

Datapoints Description

  • temperature_air_outdoor: Outdoor air temperature

  • temperature_air_outdoor_max: Outdoor air temperature upper threshold

  • temperature_air_outdoor_min: Outdoor air temperature lower threshold

  • temperature_water_chilled: Chilled water temperature

  • flow_mass_water_chilled: Chilled water mass flow rate

  • temperature_water_chilled_setpoint_max: Chilled water maximum temperature setpoint

  • temperature_water_chilled_setpoint_min: Chilled water minimum temperature setpoint

Assertions Description

  • When flow_mass_water_chilled > 0, temperature_water_chilled <= temperature_water_chilled_setpoint_max and temperature_water_chilled >= temperature_water_chilled_setpoint_min; When flow_mass_water_chilled <= 0 , always pass

Type Verification Description

Rule-based

Assertions Type

Pass