AutomaticOADamperControl
Brief Description
Hvac system shall be turned on and off everyday
Index Description
Section 6.4.3.4.2 in 90.1-2016
Datapoints Description
o: Number of occupants
m_oa: System outdoor air volume flow rate
m_ea: System exhaust air volume flow rate
eco_onoff: System air-side economizer status
tol_o: Tolerance for the number of occupants
tol_m_oa: Tolerance for the outdoor air volume flow rate
tol_m_ea: Tolerance for the exhaust air volume flow rate
Assertions Description
if no_of_occ <= 0 + tol and m_ea + m_oa > 0 and eco_onoff = 0, then false else pass
Type Verification Description
Procedure-based
Assertions Type
Pass