EconomizerHighLimitD

Brief Description

Differential enthalpy + fixed dry bulb economizer high limit (case study)

Detailed Description

N/a

Index Description

  • Table 6.5.1.1.3 in 90.1-2016

Datapoints Description

  • T_oa_db: OA dry bulb temperature

  • oa_threshold: OA dry bulb threshold

  • oa_min_flow: OA minimum airflow setpoint

  • oa_flow: OA airflow

  • oa_enth: OA enthalpy

  • ret_a_enth: Return air enthalpy

Assertions Description

  • oa_flow > oa_min_flow) AND ((ret_a_enth < oa_enth) OR (T_oa_db > oa_threshold))

Type Verification Description

Rule-based

Assertions Type

Fail