EconomizerHighLimitD
Brief Description
Differential enthalpy + fixed dry bulb economizer high limit (case study)
Detailed Description
N/a
Index Description
Table 6.5.1.1.3 in 90.1-2016
Datapoints Description
T_oa_db: OA dry bulb temperature
oa_threshold: OA dry bulb threshold
oa_min_flow: OA minimum airflow setpoint
oa_flow: OA airflow
oa_enth: OA enthalpy
ret_a_enth: Return air enthalpy
Assertions Description
oa_flow > oa_min_flow) AND ((ret_a_enth < oa_enth) OR (T_oa_db > oa_threshold))
Type Verification Description
Rule-based
Assertions Type
Fail