EconomizerHighLimitD

Brief Description

Differential enthalpy + fixed dry bulb economizer high limit (case study)

Detailed Description

N/a

Index Description

  • Table 6.5.1.1.3 in 90.1-2016

Datapoints Description

  • temperature_air_outdoor: Outdoor air temperature

  • temperature_air_outdoor_threshold: Outdoor air temperature threshold

  • flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint

  • flow_volumetric_air_outdoor: Outdoor air volume flow

  • enthalpy_air_outdoor: Outdoor air enthalpy

  • enthalpy_air_return: Return air enthalpy

Assertions Description

  • (flow_volumetric_air_outdoor > flow_volumetric_air_outdoor_setpoint_min) AND ((enthalpy_air_return < enthalpy_air_outdoor) OR (temperature_air_outdoor > temperature_air_outdoor_threshold))

Type Verification Description

Rule-based

Assertions Type

Fail