EconomizerHighLimitD
Brief Description
Differential enthalpy + fixed dry bulb economizer high limit (case study)
Detailed Description
N/a
Index Description
Table 6.5.1.1.3 in 90.1-2016
Datapoints Description
temperature_air_outdoor: Outdoor air temperature
temperature_air_outdoor_threshold: Outdoor air temperature threshold
flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint
flow_volumetric_air_outdoor: Outdoor air volume flow
enthalpy_air_outdoor: Outdoor air enthalpy
enthalpy_air_return: Return air enthalpy
Assertions Description
(flow_volumetric_air_outdoor > flow_volumetric_air_outdoor_setpoint_min) AND ((enthalpy_air_return < enthalpy_air_outdoor) OR (temperature_air_outdoor > temperature_air_outdoor_threshold))
Type Verification Description
Rule-based
Assertions Type
Fail