G36ReturnAirDamperPositionForReturnFanDirectBuildingPressure
Brief Description
Verify that the return air damper operation follows guideline 36 recommendations for systems with return fan with direct building pressure control
Detailed Description
Verify that the return air damper operation follows the guideline 36 recommendations for supply air temperature setpoint operations
Index Description
Section 5.16.2.3 in ASHRAE Guideline 36-2021
Datapoints Description
heating_output: AHU heating coil output
cooling_output: AHU cooling coil output
max_ra_p: Maximum return air damper position
ra_p_tol: Return air damper position tolerance
ra_p: Return air damper position
Type Verification Description
Procedure-based
Assertions Type
Pass
Assertions Description
if heating_output > 0
if abs(ra_p - max_ra_p) < ra_p_tol
pass
else
fail
end
else if cooling_output > 0
if abs(ra_p - 0) < ra_p_tol
pass
else
fail
end
else if abs(ra_p - (1 - rea_p) * max_ra_p) < ra_p_tol
pass
else
fail
end