G36MinOAwEconomizer

Brief Description

G36 minimum outdoor air control when economizer is active

Index Description

  • Section 5.16 in Guideline 36-2021

Datapoints Description

  • outdoor_air_temp: outdoor air temperature

  • economizer_high_limit_sp: economizer lockout high limit set point

  • outdoor_damper_command: outdoor air damper command

  • min_oa_p: minimum outdoor air damper position set point

  • min_oa_sp: minimum outdoor air flow rate setpoint

  • outdoor_air_flow: outdoor air flow rate

  • sys_mode: AHU system mode mode, enumeration of [‘occupied’, ‘unoccupied’, ‘cooldown’, ‘warmup’, ‘setback’, ‘setup’]

Assertions Description

  • if not economizer_lockout(outdoor_air_temp, economizer_high_limit_sp) and sys_mode == ‘occupied’:

  • if oudoor_damper_command >= MinOA-P and outdoor_air_flow >= MinOAsp:

  • pass

  • else:

  • fail

  • else:

  • untested

Type Verification Description

Rule-based

Assertions Type

Pass