G36MinOAwEconomizer
Brief Description
G36 minimum outdoor air control when economizer is active
Index Description
Section 5.16 in Guideline 36-2021
Datapoints Description
outdoor_air_temp: outdoor air temperature
economizer_high_limit_sp: economizer lockout high limit set point
outdoor_damper_command: outdoor air damper command
min_oa_p: minimum outdoor air damper position set point
min_oa_sp: minimum outdoor air flow rate setpoint
outdoor_air_flow: outdoor air flow rate
sys_mode: AHU system mode mode, enumeration of [‘occupied’, ‘unoccupied’, ‘cooldown’, ‘warmup’, ‘setback’, ‘setup’]
Assertions Description
if not economizer_lockout(outdoor_air_temp, economizer_high_limit_sp) and sys_mode == ‘occupied’:
if oudoor_damper_command >= MinOA-P and outdoor_air_flow >= MinOAsp:
pass
else:
fail
else:
untested
Type Verification Description
Rule-based
Assertions Type
Pass