G36MinOAwEconomizer
Brief Description
G36 minimum outdoor air control when economizer is active
Index Description
Section 5.16 in Guideline 36-2021
Datapoints Description
temperature_air_outdoor: Outdoor air temperature
temperature_air_economizer_limit: Economizer lockout temperature limit
position_damper_air_outdoor: Outdoor air damper position
position_damper_air_outdoor_min: Minimum outdoor air damper position
flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint
flow_volumetric_air_outdoor: Outdoor air volume flow
mode_system: System operation mode
Assertions Description
if not economizer_lockout(temperature_air_outdoor, temperature_air_economizer_limit) and mode_system == ‘occupied’:
if position_damper_air_outdoor >= position_damper_air_outdoor_min and flow_volumetric_air_outdoor >= flow_volumetric_air_outdoor_setpoint_min:
pass
else:
fail
else:
untested
Type Verification Description
Rule-based
Assertions Type
Pass