G36OutdoorAirDamperPositionForReturnFanDirectBuildingPressure

Brief Description

Verify that the outdoor air damper operation follows guideline 36 recommendations for systems with return fan with direct building pressure control

Detailed Description

Verify that the outdoor air damper operation follows the guideline 36 recommendations for supply air temperature setpoint operations

Index Description

  • Section 5.16.2.3 in ASHRAE Guideline 36-2021

Datapoints Description

  • oa_p: Outdoor air damper position

  • max_oa_p: Maximum outdoor air damper position

  • oa_p_tol: Outdoor air damper position tolerance

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • if abs(oa_p - max_oa_p) < oa_p_tol

  • pass

  • else

  • fail

  • end