G36OutdoorAirDamperPositionForReturnFanDirectBuildingPressure
Brief Description
Verify that the outdoor air damper operation follows guideline 36 recommendations for systems with return fan with direct building pressure control
Detailed Description
Verify that the outdoor air damper operation follows the guideline 36 recommendations for supply air temperature setpoint operations
Index Description
Section 5.16.2.3 in ASHRAE Guideline 36-2021
Datapoints Description
position_damper_air_outdoor: Outdoor air damper position
position_damper_air_outdoor_max: Maximum outdoor air damper position
Type Verification Description
Procedure-based
Assertions Type
Pass
Assertions Description
if abs(position_damper_air_outdoor - position_damper_air_outdoor_max) < 0
pass
else
fail
end