G36FreezeProtectionStage1
Brief Description
G36 freeze protection stage 1 requirements
Index Description
Section 5.16.12.1. in Guideline 36-2021
Datapoints Description
temperature_air_supply_setpoint: Supply air temperature
position_damper_air_outdoor: Outdoor air damper position
position_damper_air_outdoor_min: Minimum outdoor air damper position
Assertions Description
if temperature_air_supply_setpoint < 4.4 (continuously 5 minutes) and position_damper_air_outdoor > position_damper_air_outdoor_min:
fail
elif position_damper_air_outdoor > position_damper_air_outdoor_min and not (temperature_air_supply_setpoint > 7 (continuously 5 minutes)):
fail
else:
pass
if never (temperature_air_supply_setpoint < 4.4 (continuously 5 minutes)):
untested
Type Verification Description
Rule-based
Assertions Type
Pass