G36FreezeProtectionStage1

Brief Description

G36 freeze protection stage 1 requirements

Index Description

  • Section 5.16.12.1. in Guideline 36-2021

Datapoints Description

  • temperature_air_supply_setpoint: Supply air temperature

  • position_damper_air_outdoor: Outdoor air damper position

  • position_damper_air_outdoor_min: Minimum outdoor air damper position

Assertions Description

  • if temperature_air_supply_setpoint < 4.4 (continuously 5 minutes) and position_damper_air_outdoor > position_damper_air_outdoor_min:

  • fail

  • elif position_damper_air_outdoor > position_damper_air_outdoor_min and not (temperature_air_supply_setpoint > 7 (continuously 5 minutes)):

  • fail

  • else:

  • pass

  • if never (temperature_air_supply_setpoint < 4.4 (continuously 5 minutes)):

  • untested

Type Verification Description

Rule-based

Assertions Type

Pass