HeatPumpSupplementalHeatLockout
Brief Description
Supplemental heating coil should be off when the heat pump can meet the load by itself
Index Description
Section 6.4.3.5 Heat Pump Auxiliary Heat Control and 6.3.2.h Criteria in 90.1-2016
Datapoints Description
capacity_full_load: Heating Coil Reference Capacity
load_operation: Heating Coil Runtime Fraction
capacity_modifier_temperature: Heating Coil Heating Rate
power_heating_supplemental: Supplemental Heating Rate
capacity_modifier_fraction_flow: Heating Capacity Function of Flow Fraction Curve
load_defrost: Defrost load on the heating coil
Assertions Description
If capacity_full_load * capacity_modifier_temperature >= load_operation and power_heating_supplemental == 0 then pass else fail
Type Verification Description
Rule-based
Assertions Type
Pass