G36CoolingOnlyTerminalBoxHeatingAirflowSetpoint

Brief Description

Cooling only terminal box airflow control when the zone state is heating following the guideline 36 recommendations

Index Description

  • Section 5.5.5.3 in ASHRAE Guideline 36-2021

Datapoints Description

  • mode_system: System operation mode

  • state_zone: Zone state (heating, cooling, or deadband)

  • flow_volumetric_air_cool_max: Maximum cooling airflow setpoint

  • flow_volumetric_air_heat_max: Maximum heating airflow setpoint

  • flow_volumetric_air_setpoint_min: Minimum airflow setpoint during occupied mode

  • flow_volumetric_air_setpoint: Airflow setpoint

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • switch mode_system

  • case ‘occupied’

  • heating_maximum = flow_volumetric_air_heat_max

  • minimum = v_min

  • case ‘cooldown’, ‘setup’, ‘unoccupied’

  • heating_maximum = 0

  • minimum = 0

  • case ‘warmup’, ‘setback’

  • heating_maximum = flow_volumetric_air_cool_max

  • minimum = 0

  • if minimum <= flow_volumetric_air_setpoint <= heating_maximum

  • pass

  • else

  • fail

  • end