G36CoolingOnlyTerminalBoxHeatingAirflowSetpoint

Brief Description

Cooling only terminal box airflow control when the zone state is heating following the guideline 36 recommendations

Index Description

  • Section 5.5.5.3 in ASHRAE Guideline 36-2021

Datapoints Description

  • operation_mode: System operation mode

  • zone_state: Zone state (heating, cooling, or deadband (not in either heating or cooling))

  • v_cool_max: Zone maximum cooling airflow setpoint

  • v_heat_max: Zone maximum heating airflow setpoint

  • v_min: Occupied zone minimum airflow setpoint

  • v_spt: Active airflow setpoint

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • switch operation_mode

  • case ‘occupied’

  • heating_maximum = v_heat_max

  • minimum = v_min

  • case ‘cooldown’, ‘setup’, ‘unoccupied’

  • heating_maximum = 0

  • minimum = 0

  • case ‘warmup’, ‘setback’

  • heating_maximum = v_cool_max

  • minimum = 0

  • if minimum <= v_spt <= heating_maximum

  • pass

  • else

  • fail

  • end