MZSystemOccupiedStandbyVentilationZoneControl
Brief Description
Multizone system zone standby model ventilation control
Datapoints Description
zone_is_standby_mode: Flag indicating that the zone targeted by the verification is in occupied standby mode
m_oa_requested_by_system: System outdoor air setpoint
m_oa_zone_requirement: Outdoor air required by the targeted zone
Assertions Description
If the targted zone is in standby mode and if the difference between the outdoor air setpoint and the last reported outdoor air setpoint when the zone was not in standby mode is greater than the outdoor air required for the zone the verification passes, it otherwise fails.
Type Verification Description
Procedure-based
Assertions Type
Pass