GuestRoomControlVent

Brief Description

Verify whether there is guest room outdoor airflow control during operation hours

Index Description

  • Section 6.4.3.3.5.2 in 90.1-2016

Datapoints Description

  • damper_sch: Damper Schdule

  • m_oa_fraction: Air System Outdoor Air Flow Fraction

  • O_sch: Occupant schedule

  • m_oa_heat_design: Design Heating Air Flow Rate

  • m_oa_cool_design: Design Cooling Air Flow Rate

  • volume: Zone Volume

  • v_outdoor_per_zone: Outdoor Air Flow per Zone Floor Area

  • tol_occ: Tolerence for occupant Schedule

  • tol_oa_flow: Tolerance for Outdoor Airflow

Assertions Description

  • Check the two different airflow control logics when the room is/isn’t rented out

Type Verification Description

Rule-based

Assertions Type

Pass