G36SimultaneousHeatingCooling

Brief Description

Verifiy that both the heating and cooling coil are not operating at the same time

Index Description

  • Section 5.16.2.3 in ASHRAE Guideline 36-2021

Datapoints Description

  • heating_output: AHU heating coil output

  • cooling_output: AHU cooling coil output

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • if heating_output > 0 and cooling_output > 0

  • fail

  • else

  • pass

  • end