ZoneHeatingResetDepth
Brief Description
Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required to maintain zone temperatures above an adjustable heating set point at least 10°f below (will be 60°f) the occupied heating set point. (case study)
Index Description
Section 6.4.3.3.2 in 90.1-2016
Datapoints Description
T_heat_set: Zone Thermostat Heating Setpoint Temperature
Assertions Description
if max(T_heat_set) - min(T_heat_set) >= 10F, then pass
Type Verification Description
Procedure-based
Assertions Type
Pass