ZoneHeatingResetDepth

Brief Description

Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required to maintain zone temperatures above an adjustable heating set point at least 10°f below (will be 60°f) the occupied heating set point. (case study)

Index Description

  • Section 6.4.3.3.2 in 90.1-2016

Datapoints Description

  • T_heat_set: Zone Thermostat Heating Setpoint Temperature

Assertions Description

  • if max(T_heat_set) - min(T_heat_set) >= 10F, then pass

Type Verification Description

Procedure-based

Assertions Type

Pass