G36TerminalBoxCoolingMinimumAirflow

Brief Description

Terminal box in cooling mode needs maintain minimum airflow when supply air temperature is high following the guideline 36 recommendations

Index Description

  • Section 5.5.5.1.a in Guideline 36-2021

  • Section 5.6.5.1.a in Guideline 36-2021

Datapoints Description

  • operation_mode: System operation mode

  • zone_state: Zone state (heating, cooling, or deadband (not in either heating or cooling))

  • v_min: Occupied zone minimum airflow setpoint

  • ahu_sat_spt: AHU supply air temperature setpoint

  • v_spt: Active airflow setpoint

  • v_spt_tol: Airflow setpoint tolerance

  • room_temp: Room temperature

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • if ahu_sat_spt <= room_temp:

  • untested

  • else:

  • switch operation_mode

  • case ‘occupied’

  • minimum = v_min

  • case ‘cooldown’, ‘setup’, ‘warmup’, ‘setback’, ‘unoccupied’

  • minimum = 0

  • if v_spt - v_spt_tol > minimum:

  • fail

  • else:

  • pass