G36TerminalBoxCoolingMinimumAirflow

Brief Description

Terminal box in cooling mode needs maintain minimum airflow when supply air temperature is high following the guideline 36 recommendations

Index Description

  • Section 5.5.5.1.a in Guideline 36-2021

  • Section 5.6.5.1.a in Guideline 36-2021

Datapoints Description

  • mode_system: System operation mode

  • state_zone: Zone state (heating, cooling, or deadband)

  • flow_volumetric_air_setpoint_min: Minimum airflow setpoint during occupied mode

  • temperature_air_supply_setpoint: Supply air temperature setpoint

  • flow_volumetric_air_setpoint: Airflow setpoint

  • temperature_air_room: Room temperature

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • if temperature_air_supply_setpoint <= temperature_air_room:

  • untested

  • else:

  • switch mode_system

  • case ‘occupied’

  • minimum = v_min

  • case ‘cooldown’, ‘setup’, ‘warmup’, ‘setback’, ‘unoccupied’

  • minimum = 0

  • if flow_volumetric_air_setpoint > minimum:

  • fail

  • else:

  • pass