G36TerminalBoxCoolingMinimumAirflow
Brief Description
Terminal box in cooling mode needs maintain minimum airflow when supply air temperature is high following the guideline 36 recommendations
Index Description
Section 5.5.5.1.a in Guideline 36-2021
Section 5.6.5.1.a in Guideline 36-2021
Datapoints Description
mode_system: System operation mode
state_zone: Zone state (heating, cooling, or deadband)
flow_volumetric_air_setpoint_min: Minimum airflow setpoint during occupied mode
temperature_air_supply_setpoint: Supply air temperature setpoint
flow_volumetric_air_setpoint: Airflow setpoint
temperature_air_room: Room temperature
Type Verification Description
Procedure-based
Assertions Type
Pass
Assertions Description
if temperature_air_supply_setpoint <= temperature_air_room:
untested
else:
switch mode_system
case ‘occupied’
minimum = v_min
case ‘cooldown’, ‘setup’, ‘warmup’, ‘setback’, ‘unoccupied’
minimum = 0
if flow_volumetric_air_setpoint > minimum:
fail
else:
pass