G36ReheatTerminalBoxHeatingCoilTracking
Brief Description
Terminal box with reheat heating coil tracking discharge temperature at setpoint following the guideline 36 recommendations
Index Description
Section 5.6.5.3 c in ASHRAE Guideline 36-2021
Datapoints Description
mode_system: System operation mode
command_coil_heat: Heating coil command
temperature_air_discharge: Discharge air temperature
temperature_air_discharge_setpoint: Discharge air temperature setpoint
Type Verification Description
Procedure-based
Assertions Type
Pass
Assertions Description
only check the following if mode_system is heating
if abs(temperature_air_discharge_setpoint - temperature_air_discharge) >= 0 (less than 1hr):
pass
elif abs(temperature_air_discharge_setpoint - temperature_air_discharge) < 0:
pass
if temperature_air_discharge - temperature_air_discharge_setpoint >= 0 (continously) and command_coil_heat <= 1:
pass
elif temperature_air_discharge_setpoint - temperature_air_discharge >= 0 (continuously) and cmd_damper_vav >= 99:
pass
else:
fail
end