G36ReheatTerminalBoxHeatingCoilTracking

Brief Description

Terminal box with reheat heating coil tracking discharge temperature at setpoint following the guideline 36 recommendations

Index Description

  • Section 5.6.5.3 c in ASHRAE Guideline 36-2021

Datapoints Description

  • operation_mode: System operation mode

  • heating_coil_command: Heating coil command

  • dat: Discharge air temperature

  • dat_spt: Discharge air temperature setpoint

  • dat_tracking_tol: Temperature tracking tolerance

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • only check the following if operation_mode is heating

  • if abs(dat_spt - dat) >= dat_tracking_tol (less than 1hr):

  • pass

  • elif abs(dat_spt - dat) < dat_tracking_tol:

  • pass

  • if dat - dat_spt >= dat_tracking_tol (continously) and heating_coil_command <= 1:

  • pass

  • elif dat_spt - dat >= dat_tracking_tol (continuously) and vav_damper_command >= 99:

  • pass

  • else:

  • fail

  • end