G36ReheatTerminalBoxHeatingCoilTracking

Brief Description

Terminal box with reheat heating coil tracking discharge temperature at setpoint following the guideline 36 recommendations

Index Description

  • Section 5.6.5.3 c in ASHRAE Guideline 36-2021

Datapoints Description

  • mode_system: System operation mode

  • command_coil_heat: Heating coil command

  • temperature_air_discharge: Discharge air temperature

  • temperature_air_discharge_setpoint: Discharge air temperature setpoint

Type Verification Description

Procedure-based

Assertions Type

Pass

Assertions Description

  • only check the following if mode_system is heating

  • if abs(temperature_air_discharge_setpoint - temperature_air_discharge) >= 0 (less than 1hr):

  • pass

  • elif abs(temperature_air_discharge_setpoint - temperature_air_discharge) < 0:

  • pass

  • if temperature_air_discharge - temperature_air_discharge_setpoint >= 0 (continously) and command_coil_heat <= 1:

  • pass

  • elif temperature_air_discharge_setpoint - temperature_air_discharge >= 0 (continuously) and cmd_damper_vav >= 99:

  • pass

  • else:

  • fail

  • end