WLHPLoopHeatRejectionControl
Brief Description
Water-loop heat pump heat rejection control
Index Description
Section 6.5.2.2.3 (a) in 90.1-2016
Datapoints Description
T_max_heating_loop: maximum temperature of heating loop
T_min_cooling_loop: minimum temperature of cooling loop
m_pump: Pump Mass Flow Rate
tol: Tolerance for water-loop temperature difference
Assertions Description
If the temperature difference between the maximum heating loop and minimum heating loop when the pump runs is greater than 11.11 °C, then pass else fail
Type Verification Description
Procedure-based
Assertions Type
Pass