WLHPLoopHeatRejectionControl

Brief Description

Water-loop heat pump heat rejection control

Index Description

  • Section 6.5.2.2.3 (a) in 90.1-2016

Datapoints Description

  • T_max_heating_loop: maximum temperature of heating loop

  • T_min_cooling_loop: minimum temperature of cooling loop

  • m_pump: Pump Mass Flow Rate

  • tol: Tolerance for water-loop temperature difference

Assertions Description

  • If the temperature difference between the maximum heating loop and minimum heating loop when the pump runs is greater than 11.11 °C, then pass else fail

Type Verification Description

Procedure-based

Assertions Type

Pass