WLHPLoopHeatRejectionControl

Brief Description

Water-loop heat pump heat rejection control

Index Description

  • Section 6.5.2.2.3 (a) in 90.1-2016

Datapoints Description

  • temperature_water_heating_max: Maximum heating loop temperature

  • temperature_water_cooling_min: Minimum cooling loop temperature

  • flow_mass_water_pump: Pump mass flow rate

Assertions Description

  • If the temperature difference between the maximum heating loop and minimum heating loop when the pump runs is greater than 11.11 °C, then pass else fail

Type Verification Description

Procedure-based

Assertions Type

Pass