WLHPLoopHeatRejectionControl
Brief Description
Water-loop heat pump heat rejection control
Index Description
Section 6.5.2.2.3 (a) in 90.1-2016
Datapoints Description
temperature_water_heating_max: Maximum heating loop temperature
temperature_water_cooling_min: Minimum cooling loop temperature
flow_mass_water_pump: Pump mass flow rate
Assertions Description
If the temperature difference between the maximum heating loop and minimum heating loop when the pump runs is greater than 11.11 °C, then pass else fail
Type Verification Description
Procedure-based
Assertions Type
Pass