ZoneCoolingResetDepth ==================================================================== Brief Description ------------------------------------------------------------------------------- Cooling systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the mechanical cooling system as required to maintain zone temperatures below an adjustable cooling set point at least 5°f above the occupied cooling set point or to prevent high space humidity levels. (case study) Index Description ------------------------------------------------------------------------------- * Section 6.4.3.3.2 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_zone_cool_setpoint: Zone cooling temperature setpoint Assertions Description ------------------------------------------------------------------------------- * if max(temperature_air_zone_cool_setpoint) - min(temperature_air_zone_cool_setpoint) >= 5F, then pass Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass