VAVStaticPressureSensorLocation ==================================================================== Brief Description ------------------------------------------------------------------------------- Vav static pressure sensor location requirement Index Description ------------------------------------------------------------------------------- * Section 6.5.3.2.2 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * pressure_static_setpoint: Static pressure setpoint Assertions Description ------------------------------------------------------------------------------- * if static pressure setpoint is no greater than 1.2 in of water (298.608 Pa) then pass else fail Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass