HeatRejectionFanVariableFlowControlsCells ==================================================================== Brief Description ------------------------------------------------------------------------------- Heat rejection fan variable flow controls cells Index Description ------------------------------------------------------------------------------- * Section 6.5.5.2.2 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * number_cells_coolingtower_operation: Number of operating cooling tower cells * number_cells_coolingtower: Number of cooling tower cells * flow_mass_coolingtower: Cooling tower mass flow rate * flow_mass_coolingtower_design: Cooling tower design mass flow rate * fraction_flow_min_cell: Minimum flow fraction per cooling tower cell * power_fan_coolingtower: Cooling tower fan power Assertions Description ------------------------------------------------------------------------------- * if the number of operating cooling tower cells is equal to the maximum number of cooling tower cells then pass else fail Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass