HeatRejectionFanVariableFlowControl ==================================================================== Brief Description ------------------------------------------------------------------------------- The cooling tower fan power is 30% of the design value at 50% flow Index Description ------------------------------------------------------------------------------- * Section 6.5.5.2.1 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * power_fan_coolingtower: Cooling tower fan power * power_fan_coolingtower_design: Cooling tower design fan power * ratio_flow_coolingtower: Cooling tower airflow ratio * flow_volumetric_air_coolingtower_design: Cooling tower design airflow Assertions Description ------------------------------------------------------------------------------- * Verify that at 5% flow, the cooling tower fan power is 30% of the design value. Since simulation results might not include that exact point, we use a regression based approach to determining if the code requirement is met Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass