G36SupplyFanStatus ==================================================================== Brief Description ------------------------------------------------------------------------------- G36 supply fan on/off requirements Index Description ------------------------------------------------------------------------------- * Section 5.16.1.1. in Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * mode_system: System operation mode * flag_reheat_perimeter: Flag indicating VAV-reheat boxes on perimeter zones * status_fan_supply: Supply fan status Assertions Description ------------------------------------------------------------------------------- * if flag_reheat_perimeter == True: * if mode_system != 'unoccupied' and status_fan_supply == 'off': * fail * * else: * if mode_system in ['occupied', 'setup', 'cooldown'] and status_fan_supply == 'off': * fail * * if ['occupied', 'unoccupied'] in mode_system: * pass * else: * untested Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass