G36MinOAwoEconomizer ==================================================================== Brief Description ------------------------------------------------------------------------------- G36 minimum outdoor air control when economizer is in lockout Index Description ------------------------------------------------------------------------------- * Section 5.16 in Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_outdoor: Outdoor air temperature * temperature_air_economizer_limit: Economizer lockout temperature limit * position_damper_air_outdoor: Outdoor air damper position * position_damper_air_return: Return air damper position * flow_volumetric_air_outdoor: Outdoor air volume flow * flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint * mode_system: System operation mode Assertions Description ------------------------------------------------------------------------------- * if economizer_lockout(temperature_air_outdoor, temperature_air_economizer_limit) and mode_system == 'occupied': * if flow_volumetric_air_outdoor < flow_volumetric_air_outdoor_setpoint_min (continuously (e.g. fall below the sp for a consecutive 1 hr)): * if position_damper_air_outdoor == 100 and position_damper_air_return == 0: * pass * else: * fail * elif flow_volumetric_air_outdoor > flow_volumetric_air_outdoor_setpoint_min (continuously): * if position_damper_air_outdoor == 0 and position_damper_air_return == 100: * pass * else: * fail * else: * pass (essentially untested yet) * else: * untested Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass