G36FreezeProtectionStage1 ==================================================================== Brief Description ------------------------------------------------------------------------------- G36 freeze protection stage 1 requirements Index Description ------------------------------------------------------------------------------- * Section 5.16.12.1. in Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_supply_setpoint: Supply air temperature * position_damper_air_outdoor: Outdoor air damper position * position_damper_air_outdoor_min: Minimum outdoor air damper position Assertions Description ------------------------------------------------------------------------------- * if temperature_air_supply_setpoint < 4.4 (continuously 5 minutes) and position_damper_air_outdoor > position_damper_air_outdoor_min: * fail * elif position_damper_air_outdoor > position_damper_air_outdoor_min and not (temperature_air_supply_setpoint > 7 (continuously 5 minutes)): * fail * else: * pass * * if never (temperature_air_supply_setpoint < 4.4 (continuously 5 minutes)): * untested Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Pass