G36CoolingOnlyTerminalBoxHeatingAirflowSetpoint ==================================================================== Brief Description ------------------------------------------------------------------------------- Cooling only terminal box airflow control when the zone state is heating following the guideline 36 recommendations Index Description ------------------------------------------------------------------------------- * Section 5.5.5.3 in ASHRAE Guideline 36-2021 Datapoints Description ------------------------------------------------------------------------------- * mode_system: System operation mode * state_zone: Zone state (heating, cooling, or deadband) * flow_volumetric_air_cool_max: Maximum cooling airflow setpoint * flow_volumetric_air_heat_max: Maximum heating airflow setpoint * flow_volumetric_air_setpoint_min: Minimum airflow setpoint during occupied mode * flow_volumetric_air_setpoint: Airflow setpoint Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass Assertions Description ------------------------------------------------------------------------------- * switch mode_system * case 'occupied' * heating_maximum = flow_volumetric_air_heat_max * minimum = v_min * case 'cooldown', 'setup', 'unoccupied' * heating_maximum = 0 * minimum = 0 * case 'warmup', 'setback' * heating_maximum = flow_volumetric_air_cool_max * minimum = 0 * * if minimum <= flow_volumetric_air_setpoint <= heating_maximum * pass * else * fail * end