FanStaticPressureResetControl ==================================================================== Brief Description ------------------------------------------------------------------------------- The set point is reset lower until one zone damper is nearly wide open Index Description ------------------------------------------------------------------------------- * Section 6.5.3.2.3 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * pressure_static_setpoint: Static pressure setpoint * position_damper_vav: VAV damper position Assertions Description ------------------------------------------------------------------------------- * if position_damper_vav(n) (n=1,2,...,N) < 0.9 and pressure_static_setpoint(t) > pressure_static_setpoint(t-1), then fail else pass Type Verification Description ------------------------------------------------------------------------------- Procedure-based Assertions Type ------------------------------------------------------------------------------- Pass