EconomizerHighLimitB ==================================================================== Brief Description ------------------------------------------------------------------------------- Differential dry bulb economizer high limit Detailed Description ------------------------------------------------------------------------------- Check the 90.1-2016 table Index Description ------------------------------------------------------------------------------- * Table 6.5.1.1.3 in 90.1-2016 Datapoints Description ------------------------------------------------------------------------------- * temperature_air_outdoor: Outdoor air temperature * temperature_air_return: Return air temperature * flow_volumetric_air_outdoor_setpoint_min: Minimum outdoor air volume flow setpoint * flow_volumetric_air_outdoor: Outdoor air volume flow Assertions Description ------------------------------------------------------------------------------- * (flow_volumetric_air_outdoor > flow_volumetric_air_outdoor_setpoint_min) AND (temperature_air_return < temperature_air_outdoor) Type Verification Description ------------------------------------------------------------------------------- Rule-based Assertions Type ------------------------------------------------------------------------------- Fail